Transmitter programmable thermocouple
Assembly: sounding head DIN “B” Input: thermocouples B, E, J, K, L, NR, R, S, T, U, W3, W5, LR Output: 4-20 my - technical 2 wire Simple and fast programming Compensation of cold welding (CSF) carried out using a temperature gauge integrated into the module continuous Checking of the safeguarded data Temperature of use: -40 to +85 °C Supply voltage DC: 7,2 to 35 Vcc Internal consumption: 25 mW to 0,8 W Fall of voltage: 7,2 Vcc Voltage of insulation, test/operation: 1,5 kVca/50 Vca Time of heating: 5 minutes Signal-to-noise report/ratio: Min. 60 dB Answer time (programmable): 1 to 60 S Checking of Eeprom < 3,5 S Dynamics of the input signal: 18 bit Dynamics of the output signal: 16 bit Temperature of calibration: 20 to 28 °C Absolute accuracy ≤ ± 0,05% of EC. Temperature coefficient ≤ ± 0,01% of the EC/°C Effect of a variation of the voltage of voltage supply < 0,005% of EC/Vcc Vibration IEC 68-2-6 Test FC Humidity < 95% HR Dimensions: Ø 44 mm X 20,2 mm Sealing (case/connector block): IP68/IP00 Weight: 50 G 5 years of guarantee Approval ATEX : KEMA 06ATEX0062 X
II 1 G Ex ia IIC II 1 D Ex iaD temperature amb. max. (T1…T4) : 85°C temperature amb. max. (T5 and T6) : 60°C Zones of application = 0, 1, 2, 20, 21, 22 |
|
|
|